It is important to follow the general principles before installation and during use after installation.
Installation diagram
| No. | Item | No. | Item |
|---|---|---|---|
| 1 | Return direction | 8 | Heat meter connector |
| 2 | Return line | 9 | Valve body |
| 3 | Ball valve | 10 | Ball valve |
| 4 | Return line straight pipe | 11 | Supply line straight pipe |
| 5 | Heat meter connector | 12 | Supply line ball valve |
| 6 | Calculator | 13 | Supply line straight pipe |
| 7 | Flow sensor | 14 | Supply direction |
1.1 Environmental requirements for installation
DIGITERMO is designed to operate indoors in a non-condensing environment at 5–55 °C. The heat meter must not be exposed to any mechanical stress in the installation and must be protected against pressure shocks. Humidity at the installation site must not exceed 85% (no condensation).
Care should be taken to keep the heat meter away from electromagnetic interference (fluorescent lighting, electronic switches, electric motors, etc.).
All control cables must be routed separately from each other and not parallel to power cables. Install at least 25 cm away from signal cables and other electromagnetic sources. If 2 or more meters are installed in the same place, they must be at least 135 mm apart.
1.2 Before installation
Flush the system before installing the flow sensor of the heat meter; dirt, stones and other foreign matter must be removed. Cavitation must be avoided in the system design. If there is a risk of frost, drain the system and remove the meter if necessary. If the water is dirty, install a strainer in the line before the meter.
1.3 Heat meter installation steps
- Flush the pipe system thoroughly before installing the meter.
- Leave a straight run of 10×DN (according to the meter diameter) on the inlet side of the flow sensor and 5×DN on the outlet side.
- Fit the union connections with suitable sealing gaskets on both sides of the heat meter and keep them aligned with the pipe.
- Install valves on both sides of the heat meter so the line can be shut off, and a strainer before the meter (if the water is dirty).
- After completing the above, insert the temperature sensor and seal it.
1.4 Flow sensor installation
Install the meter in the line so that the arrow on the flow body matches the flow direction. Avoid air bubbles accumulating in the meter during installation.
To prevent air remaining in the flow sensor, do not install the meter at the highest point of the system. The flow sensor MUST NOT be installed where there is swirling flow (caused by pipe bends) or pulsating flow (usually caused by pumps — the flow sensor should be installed as far away from them as possible). Directly at a pump outlet is not recommended, as air can collect there.
- A: recommended meter installation position.
- B: recommended meter installation position.
- C: installation position not recommended.
- D: installation position not accepted in open systems, accepted in closed systems.
1.5 Temperature sensor installation
For the DIGITERMO model, one temperature sensor is supplied already mounted in the flow sensor and sealed. The installation instructions for the sensor used to measure supply and return temperature are as follows:
1.5.1 Matched pairs
The sensors are colour-coded. The one marked red is normally installed in the flow/supply line; the other sensor, marked blue, is fitted on the flow body of the meter in the return line. The blue sensor leaves the factory mounted in the flow sensor and sealed.
The temperature sensors are used as a pair and must not be separated. Do not tamper with the temperature sensors in any way (shortening, replacing one, etc.).
Any such interference will cause the heat meter to measure incorrectly. The temperature sensors, produced by Jumo or Bocon, are calibrated so that the temperature difference can be measured within a specific accuracy class; a wrong pairing seriously affects measuring accuracy.
According to EN 1434 or OIML R75, the standard cable length is 1.5 or 1.2 m and must not be changed. If the sensor cable length has to be changed because of site constraints, the meter must be specially processed at the factory.
1.5.2 Installation direction
The tip of the temperature sensors must always reach the centre of the pipe cross-section. Sensors should preferably be installed symmetrically and directly. The sensor in the flow sensor comes factory-installed and sealed.
Temperature sensors must be installed where the water temperature is relatively constant, and the installation conditions for both sensors should be similar. The supply temperature sensor must be installed so that its tip is in the middle of the pipe. Temperature sensors are typically installed in a T-piece, ball valve or sensor pocket.
1.5.3 Sealing
The temperature sensors and screw connections must be sealed against manipulation, and the seals must not be damaged. Before installing the temperature sensor, place the O-ring supplied in the box into the mounting seat with gentle circular movements. Insert the sensor at the mounting point and screw it in tightly until the O-ring is fully compressed. After installation, secure the sensor against removal by unauthorised persons with a suitable seal; this DIGITERMO-branded seal is supplied in the box. This installation and sealing on the supply line is not required for the sensor in the meter’s flow body, which is factory-installed and sealed.
1.6 Calculator installation
The calculator is mounted directly on the plate of the flow sensor. The screws used on the calculator carry seals that prevent tampering. With heavy condensation or water temperatures above 90 °C, it is recommended to mount the calculator on the wall with a separate base.
The ambient temperature of the calculator must not exceed 55 °C and it must be protected from direct sunlight. It can be mounted vertically or horizontally relative to the flow sensor, and can also be detached from the flow sensor and mounted in the required position.
1.7 Check valve (non-return valve) installation
On request, the meter can be supplied with a check valve (non-return valve), which must be fitted at the water inlet of the meter.
1.8 After installation
- Test for leaks by supplying the line with cold water and slowly filling the pipe once installation is complete.
- Open the shut-off valves carefully and check the installation for leaks.
- While the system is running, check the volume value; there should be data for instantaneous flow. Check the supply and return temperatures, which should show the system temperatures.
- Run a segment test from the meter menu and make sure all icons on the meter display work correctly.
The total operating hours are calculated from the time the battery was first inserted. The date is incremented every day. As standard, the heat meter is delivered set to local Turkish time.